Cooling process

Because there is nothing more precious than your processes, for 30 years we have developed refrigeration systems combining modularity and reliability for the preservation and optimization of your production tools.

Air cooled chillers for wine applications – R410a – Scroll compression

8.6 Kw  > 178 Kw
Air cooled chillers for wine applications – R410a – Scroll compression

The WineChill range consists of 16 models designed to provide temperature regulation solutions tailored to the needs of the most demanding winemakers :

- Temperature maintenance of the harvest tank

- Thermoregulation of fermentation tanks

- Management of malolactic fermentations

- Cooling/heating of the winery

- Air conditioning/heating of associated facilities

This product line has been designed to offer great flexibility in use :

- Cooling unit with simultaneous heating/cooling capabilities through the "free" recovery of heat from the compressor, leading to an energy gain of 25%

- Fully designed to meet agro-food industry needs

- Completely adapted design for seamless integration into the winery

- Monobloc Plug-and-Play unit

Secteurs d'application

Wine/Brewery

Caractéristiques Techniques

Refrigerant R410a Refrigeration circuit 1 Scroll compressor No Frost Evaporator Plug fan

Plug and Play

The WineChill air-cooled chillers feature an integrated hydraulic kit (pump, reservoir, pressure transducer, and automatic bypass), making them ready for immediate installation in your water networks.

Compressors

High-performance Scroll compressors are specifically developed for the HFC refrigerant R410a, delivering excellent energy efficiency.

Heat Exchanger

The NoFrost exchanger patented by CTA guarantees the capability to operate with water temperatures up to 5°C without the need for glycol solution addition.

Fan & Condenser

The latest generation fan operates at limited rotation speeds and features optimized safety with an accident protection grille. Its aerodynamic profile and streamlined blades ensure high efficiency while reducing noise levels.

Control

The connected Carel regulation system allows for the management and regulation of all functions of the chilled water production unit.

No Frost Exchanger, No Risk Exchanger

The submerged design in a water tank, combined with its optimized profile in DNA cycle, prevents freezing and eliminates any risk of glycol contamination in the harvest.

Design

The design is fully adapted for integration into the winery, featuring excellent visual and acoustic discretion. The enhanced insulation of the air handling and refrigeration components significantly reduces noise levels and sound pressures.

Installation

Installation can be carried out both indoors and outdoors, depending on the winery's constraints.

Easy Maintenance

Maintenance of these units is straightforward, as all panels are fully removable, allowing for quick access to various components.

Heat Recovery

Our systems enable the recovery of heat from the compressor output, allowing for the simultaneous production of a hot source alongside a cold source (warming the tank, heating a fluid, heating the winery).

REFRIGERATION PERFORMANCE
02C103C105C108C109C110C112C115C118C220C226C230C235C240C250C455C4
Cooling capacity (1)kW8,212,316,520,924,628,834,342,449,353,557,668,697,3110,0138,0178,0
Cooling capacity (1)Fg705510583141971798321166247802951236482424194603249560590258371994646118738153155
Hot power (2)kW8,712,717,421,525,429,634,943,950,855,059,369,9100,0112,0142,0184,0
Heating power(2)Cal748610927149711849921855254683002937772437094732351023601438604296367122180158317
EER2,092,282,212,802,722,552,332,242,462,292,142,452,352,352,312,40
SEPR4,514,764,924,534,514,624,64,694,944,694,884,684,985,024,954,74
Total power consumptionkW 3,95,47,57,59,111,314,718,920,023,426,928,041,446,959,774,1
Maximum absorbed currentA9,613,318,020,422,425,829,442,044,050,854,462,983,287,6118,9156,4
Refrigeration
02C103C105C108C109C110C112C115C118C220C226C230C235C240C250C455C4
Number of compressor(s)1111111122222222
Number of refrigeration circuits1111111111111122
Power stage1111111122222222
Aeraulics
02C103C105C108C109C110C112C115C118C220C226C230C235C240C250C455C4
Number of fans1111111122222233
Fan power0,20,40,40,70,70,70,70,71,51,51,52,33,53,62,05,3
Hydraulics
02C103C105C108C109C110C112C115C118C220C226C230C235C240C250C255C4
Pump powerkW0,60,550,550,90,90,90,91,51,51,51,52,22,23,03,04,0
Water flowm3/h1,42,12,83,64,25,05,97,38,59,29,911,816,718,923,730,6
Available pressurebar2,7 / 4,52,5 / 2,82,3 / 2,82,6 / 2,92,5 / 2,92,4 / 2,92,3 / 2,92,8 / 3,12,6 / 3,12,4 / 3,12,4 / 3,12,9 / 3,52,6 / 3,52,6 / 3,02,3 / 3,02,7 / 3,6
Tank volumeL306060160160160160160290290290460460460500500
Dimensions and weight
02C103C105C108C109C110C112C115C118C220C226C230C235C240C250C455C4
Length(L)mm8309809801 2801 2801 2801 2801 2801 9301 9301 9302 5802 5802 5803 5203 520
Depth(D)mm645795795990990990990990990990990990990990990990
Height(H)mm1 4051 8201 8202 0902 0902 0902 0902 0902 1902 1902 1902 2682 2682 2682 2502 328
Shipping weightkg2002652754604804854955037467517521 0681 1191 1421 3301 471
Connection diameter''"1/2"" (DN15)""1"" (DN 25)""1"" (DN 25)""1"" 1/4 (DN 32)""1"" 1/4 (DN 32)""1"" 1/4 (DN 32)""1"" 1/4 (DN 32)""1"" 1/4 (DN 32)""1"" 1/2 (DN 40)""1"" 1/2 (DN 40)""1"" 1/2 (DN 40)""2"" (DN 50)""2"" (DN 50)""2"" (DN 50)""3"" (DN 80)""3"" (DN 80)"
Sound pressure (3)dB(A)68696968686969707072727275757575

Contact us